Email Us    
 
A glass bulb is the most reliable and simplest to use device to actuate a fire sprinkler head. A chemical liquid sealed in the glass bulb expands rapidly when exposed to rising temperatures, bursting the bulb at an accurately pre-determined temperature, thereby actuating the sprinkler.
Day-Impex manufactures a range of Glass bulbs for Fire Sprinkler Heads and other temperature-actuated mechanisms, such as fire dampers, smoke-vents, window-closers, etc.

With over 40 years experience in glass bulb technology, a bulb for every design of head and for every fire-risk application is available.

A range of sizes, with diameters from 12mm down to 2.5mm, is available in lengths to suit all sprinkler frame designs, with aesthetically pleasing results.

Extensive research into formulating chemical liquids with known, precise expansion rates, ensures that all bulbs meet specific performance standards required by Approval Authorities throughout the world.

Precision engineering and exhaustive quality control in every stage of production ensures that the 3 most critical bulb characteristics are achieved.

  • Uniform and consistent size
  • High mechanical strength
  • Highly accurate operation temperature within tight tolerances.
  • Consistent RTI values


The entire manufacturing process carries certification to the Quality Standards of ISO9001:2000, and all bulbs meet the new European Standard, EN12259.
Day-Impex Glass Bulbs Types 937 and 941 carry UL Component Recognition in various rated temperatures.
Day-Impex Glass Bulb Types 937, 941 and 817 carry LPCB Product Approvals in various rated temperatures.

The trend to make sprinklers operate faster to suppress fire and restrict spread, has seen Day-Impex develop a progression of new glass bulb designs. Reducing the bulb diameter, but maintaining strength, researching and selecting faster-expanding liquids, has resulted in new bulbs to meet every challenge including the Residential and ESFR Standards of UL, FM, EUROPE and KOFEIS in Korea.

Below is a table showing the range of Day-Impex glass bulb sizes, their operating temperatures and the most widely used Standards met by each bulb.

Please download our latest technical specification sheets for our range of Sprinkler Bulbs by clicking the links below (all downloads are PDF format):

Type 817   Type 933   Type 937   Type 941
Type 942   Type 984   Type 989

 
The Day-Impex range of Standard Glass Bulbs
BULB TYPE 826 817 937/933* 984 941/942* 989
SIZE (DIA) mm 12 8 5 4 3 2.5
TEMPERATURES top            
57°C 135°F
bulb Tick Tick Tick Tick Tick Tick
68°C 155°F
bulb Tick Tick Tick Tick Tick Tick
79°C 175°F
bulb Tick Tick Tick Tick Tick Tick
93°C 200°F
bulb Tick Tick Tick Tick Tick Tick
141°C 286°F
bulb Tick Tick Tick Tick Tick Tick
182°C 360°F
bulb Tick Tick Tick Tick    
Applications
& approvals



bottom


Standard EN12259




Standard
LPS1039
EN12259
UL199



Standard
EN12259
FM, UL199
LPS1039
(937 Only)



Standard
EN12259





Standard
EN12259
FR, FM Residential
UL-QR, KOFEIS FR
LPS1039
(941 Only)

Standard
UL-QR Residential
FM Resindential
EN12259 Residential

* Offered in a choice of two lengths

This product may also be referred to as:

  • Sprinklers
  • Frangible Bulbs
  • Glass Sprinkler Bulbs
  • Thermo Bulbs
 